Calculation of leakage inductance for high-frequency transformers
Ouyang, Ziwei ; Zhang, Jun ; Hurley, William Gerard
Ouyang, Ziwei
Zhang, Jun
Hurley, William Gerard
Identifiers
http://hdl.handle.net/10379/13371
https://doi.org/10.13025/26556
https://doi.org/10.13025/26556
Repository DOI
Publication Date
2015-10-01
Type
Article
Downloads
Citation
Ouyang, Ziwei; Zhang, Jun; Hurley, William Gerard (2015). Calculation of leakage inductance for high-frequency transformers. IEEE Transactions on Power Electronics 30 (10), 5769-5775
Abstract
Frequency-dependent leakage inductance is often observed. The high-frequency eddy current effects cause a reduction in leakage inductance. The proximity effect between adjacent layers is responsible for the reduction of leakage inductance. This paper gives a detailed analysis of high-frequency leakage inductance and proposes an accurate prediction methodology. High-frequency leakage inductances in several interleaved winding configurations are also discussed. Interleaved winding configurations actually give a smaller degree of reduction of leakage induction at high frequency. Finite-element analysis simulation and measurement validate the models.